How To Change Account Number On Fire Lite Panel: Step-by-Step Programming Guide

How To Change Account Number On Fire Lite Panel: Step-by-Step Programming Guide

Panel de Control de Liberación de Agentes Fire-Lite - Corporativo Mega

Modifying the central station transmitter account number on a Fire-Lite Fire Alarm Control Panel (FACP) requires accessing the system's programming menu using the authorized master installer code. This technical procedure ensures that emergency signals, including alarms, troubles, and supervisory events, are accurately routed to the correct monitoring station receiver under NFPA 72 guidelines. System integrators must place the panel on test mode with the central station before initiating any program alterations to prevent accidental dispatch.


Pre-Programming Requirements & Site Preparation

Altering the Digital Alarm Communicator Transmitter (DACT) configuration on any commercial fire alarm control panel requires careful preparation. If you modify the account number while the system is active, the panel may transmit invalid codes, or the monitoring station receiver may reject the signals, generating a failure-to-communicate (FTC) trouble condition on the panel. Furthermore, local fire authorities and the National Fire Protection Association (NFPA) mandate specific procedures to maintain life-safety compliance during system service.

Before touching the panel keypad, you must identify the exact communication path used by the FACP. Older systems rely on standard Plain Old Telephone Service (POTS) copper lines, while modern installations use IP-communicators or cellular transceivers (such as the Fire-Lite IPDACT-2 or external LTE communicators). If an external cellular or IP dialer capture module is installed, the account number might need to be changed in the external communicator software interface rather than, or in addition to, the internal FACP program. Always verify the system architecture prior to beginning.



Pre-Procedure Checklist



  • Estimated Duration: 30 to 45 minutes.
  • Skill Level Required: NICET Level II or higher Fire Alarm Systems Technician.
  • Authorized Codes: Master Programming Code (Factory default is 00000 for legacy panels like the MS-9200UDLS or 88888 for newer ES-series panels).
  • Notification Protocol: Active monitoring service must be contacted to place the account on a temporary test bypass (typically 1 to 2 hours).
  • Essential Tools:

    • Fire-Lite PK-1 programming key (if applicable to legacy systems).
    • Numeric keypad access.
    • Cabinet key (typically the standardized Cat 45 key).
    • Copy of the system's central station programming sheet (containing the new account number, receiver phone numbers, and transmission format).

Step-by-Step Programming Guide to Changing the Communicator Account Number

The following steps detail the exact manual programming sequences for the most widely deployed Fire-Lite panels, including the MS-9200UDLS, MS-9600UDLS, and the newer ES-50X and ES-200X addressable fire alarm systems.



Step 1: Place the System on Test and Notify the Central Station

Before modifying any configuration settings, call the central monitoring station. Provide them with the current account number, the facility name, and your technician identification code. Request that the entire system be placed on test mode to ignore incoming signals.

Warning: Failing to place the monitoring account on test before changing DACT parameters can trigger false dispatches or register false trouble signals at the central station receiver, leading to potential municipal fines.



Step 2: Access the Master Programming Menu

Locate the main Fire Alarm Control Panel and open the outer cabinet door using the Cat 45 key. Locate the system keypad and liquid crystal display (LCD) screen.

For Legacy MS-9200UDLS / MS-9600UDLS panels:



  1. Press the Enter key on the keypad.
  2. The screen will prompt you to enter the 5-digit master code.
  3. Enter the master installer code (the default factory code is 00000). If the default code has been changed and is unknown, you must contact your company's system administrator or perform a hardware-level factory reset, which will wipe all field programming.
  4. Once the code is accepted, the screen will display the main system programming menu. Press the 1 key to select Program.

For Modern ES-50X / ES-200X panels:



  1. Press the Menu button.
  2. Use the arrow keys to scroll down to Program and press Enter.
  3. Enter the 5-digit master programming code (the default factory code is 88888).
  4. Press Enter to access the programming directory.


Step 3: Navigate to the Communicator (DACT) Settings Menu

Once inside the primary programming interface, you must navigate to the digital communicator options.

For MS-Series Panels:



  1. From the primary program screen, press the 3 key to select Communicator.
  2. Press the 1 key to select Prog Comm.
  3. The display will show options for configuration, including Primary Phone Number, Primary Account Number, Secondary Phone Number, and Secondary Account Number.

For ES-Series Panels:



  1. Use the down arrow key to navigate to System Settings and press Enter.
  2. Scroll to Communicator and press Enter.
  3. Select Communication Path or Dialing Options depending on whether the system uses standard phone lines, IP, or cellular routing.
  4. Select Account Settings to access the identifier fields.


Step 4: Program the Primary and Secondary Account Numbers

Fire-Lite panels generally require a 4-digit or 6-digit hexadecimal account number, depending on the communication format selected (such as Ademco Contact ID or SIA). Standard Ademco Contact ID typically utilizes a 4-digit account number.

To change the primary account number:



  1. Select Primary Acct or Account 1.
  2. The cursor will flash on the first digit of the existing account number.
  3. Use the numeric keypad to enter the new account number. For example, if your new central station account number is 4721, enter those digits sequentially.
  4. If your account number requires hexadecimal characters (A through F), you must use the designated scroll or key sequence. On older MS panels, you can enter hexadecimal characters by pressing the Mode key or using the up and down arrow keys to cycle past the number 9 until the desired letter appears.
  5. Once the correct digits are entered, press the Enter/Store key to save the changes to the primary account buffer.

To change the secondary account number:



  1. Select Secondary Acct or Account 2.
  2. Input the secondary account number. In almost all installations, this will match the primary account number to ensure consistent tracking across both phone lines or secondary IP pathways.
  3. Press the Enter/Store key to save the changes.

Pro-Tip: If the system is programmed to use Ademco Contact ID, do not enter any leading zeros unless they are explicitly part of the assigned 4-digit account number. If a 3-digit account number is assigned by the central station, it must be padded with a leading zero (e.g., 0352) to satisfy the panel's 4-digit requirement.



Step 5: Save Programming Changes and Exit

Once both the primary and secondary account numbers have been updated, you must systematically back out of the programming menu to write the new data to the panel's non-volatile EEPROM memory.



  1. Press the Escape (ESC) or Back key repeatedly until the system prompts you to save changes.
  2. Select Yes or press the designated key to write the new settings to memory.
  3. The panel will perform a brief system initialization and software reset. During this phase, the system may temporarily display a System Initialization or System Trouble screen.
  4. Wait for the panel to return to its Normal Standby state, displaying only the current time, date, and "System All Normal" message.


Step 6: Verify Communication with the Central Station

The modification is not complete until you verify that the panel can successfully communicate using the newly programmed account number.



  1. Locate the physical keypad and access the diagnostic menu.
  2. On modern ES panels, navigate to Menu, select Diagnostics, then select Communicator Test.
  3. Select Primary Phone / Path Test or Manual Comm Test.
  4. The panel will seize the active communication path and attempt to transmit a test signal to the receiver.
  5. Watch the LCD screen. It should display Status: Connecting, followed by Status: Handshake, and finally Status: OK or Comm Test Passed.
  6. Call the central monitoring station. Confirm that they received the manual test signal and verify that it was received under the correct new account number.

(11+) - Application for Change Mobile Number in Bank Account

(11+) - Application for Change Mobile Number in Bank Account

Fire-Lite FACP Communicator Parameters & Formats

The programming values and master access codes differ across various Fire-Lite panel generations. Below is a comparative reference table outlining default settings, character limits, and supported formats.



Fire-Lite Panel Model Default Master Code Supported Account Length Compatible Formats Memory Type
MS-5UD / MS-10UD 00000 4 Digits (Hexadecimal) Contact ID, SIA, 3+1, 4+2 EEPROM (Internal Keypad Prog)
MS-9200UDLS 00000 4 Digits (Hexadecimal) Contact ID, SIA EEPROM (Keypad or PS-Tools)
MS-9600UDLS 00000 4 Digits (Hexadecimal) Contact ID, SIA EEPROM (Keypad or PS-Tools)
ES-50X 88888 4 or 6 Digits Contact ID, SIA Flash Memory (Keypad or FS-Tools)
ES-200X 88888 4 or 6 Digits Contact ID, SIA Flash Memory (Keypad or FS-Tools)

Troubleshooting Central Station Communication Failures

If the fire alarm panel experiences issues after you modify the central station account number, consult the troubleshooting procedures below to isolate and resolve the error.



"Comm Fault" (Trouble 15 / Phone Line Failures)



  • Root Cause: The panel was programmed with an incorrect dialing format or receiver phone number, causing the FACP to fail to connect to the central station receiver. Alternatively, the panel may have dialed out using an account number that is not registered in the central station database, causing the receiver to reject the call and hang up.
  • Actionable Fix: Verify that the primary and secondary phone numbers are configured correctly, including any necessary prefixes (such as dialing 9 for an outside line). Confirm with the central station database manager that the new account number is active and set up to accept the specified format (Contact ID or SIA).


"Account Number Refused" or Formatting Conflicts



  • Root Cause: The account number contains incompatible hexadecimal characters (e.g., entering A instead of 0) or the account length does not match the receiver protocol requirements.
  • Actionable Fix: Re-enter the programming menu and confirm the account length. For standard Contact ID, ensure that you have configured a 4-digit numeric sequence. If the central station provided a 10-digit account number, verify if you are using an external IP or cellular communicator that intercepts the dialer's 4-digit code and translates it to a 10-digit account structure before sending it to the receiver.


"Locked Out of Programming" (Lost Master Code)



  • Root Cause: The default installer master code (00000 or 88888) was changed during a previous system installation and the current code is unknown, preventing access to the programming menu.
  • Actionable Fix: On legacy panels, you can bypass the master code by bridging specific terminals on the motherboard during power-up or by using a proprietary utility upload tool (such as PS-Tools) with a direct serial connection. On ES-series panels, you must perform a factory hardware restore using the designated onboard jumpers, which requires downloading and reinstalling the complete site database.

Frequently Asked Questions



What is the default programming code for a Fire-Lite panel?

The default programming code for legacy Fire-Lite panels, such as the MS-9200UDLS and MS-5UD, is 00000. For newer addressable systems, such as the ES-50X and ES-200X, the default installer master code is 88888.



Can I program a letter into the Fire-Lite account number?

Yes. Fire-Lite panels support hexadecimal digits (A through F) in the account number fields. To input letters, use the up and down arrow keys to scroll past the number 9, or press the designated Mode button to toggle alphabetical input.



Do I need to change the account number on the IPDACT if I change it on the panel?

Yes. If your system utilizes an external IP or cellular communicator, such as an IPDACT-2 or a Honeywell IPGSM-DP, the communicator often has its own internal account settings. You must update both the FACP internal programming and the external communicator configuration to ensure they match and compile correct data packets.



Why does my Fire-Lite panel show a "Trouble" light after changing the account number?

This typically indicates a communication failure (FTC). The panel attempted to send a test signal with the new account number, but the central station receiver did not acknowledge the transmission, or the physical telephone lines were disconnected during programming. Perform a manual communication test to clear the trouble latch.

Professional Low-Voltage and Fire Alarm Solutions

If your facility requires expert assistance with fire alarm system modifications, reprogramming, or code compliance updates, reach out to our certified low-voltage integration team. Our factory-trained specialists provide comprehensive maintenance, emergency repairs, and NFPA-compliant testing services tailored to your building's specific safety requirements.


Fire-Lite MS4424 Fire Alarm Control Panel | Download fire alarm documents

Fire-Lite MS4424 Fire Alarm Control Panel | Download fire alarm documents

Read also: What you need to know about the Sowton Park and Ride